Simple
- Can be integrated into existing and new PV plants
- On-site configuration of grid type
Flexible
- Capacities from 5 kW to 100 kW available
Efficient
- Small battery due to integration of the PV plant
- Consistently high PV efficiency
Reliable
- Certified protection concepts for TN and TT grids
- Automatic switching in approx. just 20 milliseconds
| Sunny Backup System M |
Sunny Backup System L |
Sunny Backup System XL (only for TN) |
|
| Output: loads | |||
| Nominal power / current during grid operation | 7.4 kW / 32 A at 35°C | 35 kW / 3 x 50 A at 35°C | 110 kW / 3 x 160 A at 25°C |
| Max. power / current in grid operation for 30 min | 8.9 kW / 38 A at 35°C | 41 kW / 3 x 60 A at 35°C | — / — |
| Maximum fuse link | 40 A | 63 A | 160 A |
| Backup power (duration / 30 min / 1 min) | 5 kW / 6.5 kW / 8.4 kW | 15 kW / 19.5 kW / 25.2 kW | 60 kW / 78 kW / 100 kW |
| Number of phases (grid operation / backup operation) | 3 / 3 x 1~ | 3 / 3 | 3 / 3 |
| Voltage (range) | 230 V (187 V – 253 V) | 230 V (187 V – 253 V) | 230 V (187 V – 253 V) |
| Frequency (range) | 50 Hz (45 Hz ... 55 Hz) | 50 Hz (45 Hz ... 55 Hz) | 50 Hz (45 Hz ... 55 Hz) |
| Permissible grid structure | TN / TT | TN / TT | TN |
| Typical interruption time during grid failure | 20 ms | 20 ms | 20 ms |
| Input PV plant | |||
| Nominal AC-PV power / current | 5.7 kW / 25 A at 35°C | 28 kW / 3 x 40 A at 35°C | 110 kW / 3 x 160 A at 25°C |
| Maximum size of fuse link | 32 A | 50 A | 160 |
| Compatible PV inverter | all SB and SMC-A | all SB, SMC and Tripower | all SB, SMC and Tripower |
| Input battery | |||
| Nominal voltage | 48 V | 48 V | 48 V |
| Battery type | VRLA / FLA / NiCd | VRLA / FLA / NiCd | VRLA / FLA / NiCd |
| Efficiency / self-consumption | |||
| Max. efficiency in backup operation | 94 % | 95 % | 95 % |
| Self-consumption day / night (silent mode) | 48 W / 32 W | 103 W / 69 W | 360 W / 230 W |
| Protection devices | |||
| DC reverse polarity protection / deep discharge protection | yes / yes | yes / yes | yes / yes |
| AC short circuit / AC overload | yes / yes | yes / yes | yes / yes |
| Grid monitoring (SMA Grid Guard) / galvanic separation | yes / yes | yes / yes | yes / yes |
| Protection class (according to IEC 62103) | I | I | I |
| Overvoltage category (according to IEC 60664) | III | III | III |
| General data | |||
| SBU dimensions (W / H / D) | 467 / 612 / 235 mm | 467 / 612 / 235 mm | 467 / 612 / 235 mm |
| AS-Box dimensions (W / H / D) | 550 / 950 / 225 mm | 800 / 950 / 225 mm | 1000 / 1600 / 300 mm |
| SBU / AS-Box weight | 63 kg / 50 kg | 63 kg / 70 kg | 63 kg / 180 kg |
| Operating temperature range | -25°C ... +50°C | -25°C ... +50°C | -25°C ... +50°C |
| Climatic class (according to IEC 60721-2-1) | 4K4H | 4K4H | 4K4H |
| SBU / AS-Box degree of protection (IP) (according to IEC 60529) | IP30 / IP54 | IP30 / IP54 | IP30 / IP65 |
| Features / function | |||
| Integrated bypass in case of fault / test operation | yes / yes | yes / yes | yes / yes |
| State of charge calculation | yes | yes | yes |
| Communication line | 5 m | 5 m | 5 m |
| Array input (nominal power) | Optional (32 A at 35°C) | Optional (40 A at 35°C) | Optional (160 A at 25°C) |
| SBU / AS-Box warranty (5 / 10 / 15 / 20 / 25 years) | yes / opt. / opt. / opt. / opt. | yes / opt. / opt. / opt. / opt. | yes / opt. / opt. / opt. / opt. |
| 240 V voltage range (192.5 - 260.0 V) | opt. | opt. | opt. |
| Certificate and approvals (further approvals on request) | CE, VDE 0126-1-1 | CE, VDE 0126-1-1 | CE, VDE 0126-1-1 |
| Accessories | |||
| Battery cables | opt. | opt. | opt. |
| Battery fuse "BATFUSE" | opt. | opt. | opt. |
| Interfaces (RS485 PB) / Multicluster PB | opt. / opt. | opt. / opt. | yes / opt. |
| Type designation | SBU5000 and AS-Box-M-20 | 3 x SBU5000 and AS-Box-L-20 | 12 X SBU 5000 and AS-Box-XL |
Downloads
Language:
Data sheet
|
406 KB |
Suny Backup Set M / L / XL - Solar power – even in the event of grid failure Type: Data sheet Language: English (AU) Document number: SBUPSYS-DAU102020 Version number: 2.0 |
Technical Description
|
155 KB |
SUNNY ISLAND / SUNNY BACKUP - Multicluster Update Type: Technical Description Language: International Document number: ClusterUpdate-TXX094010 Version number: 1.0 |
|
204 KB |
SUNNY BACKUP 5000 - Einsatz des Sunny Backup in TT-Systemen / Akustische Warnung Type: Technical Description Language: International Document number: SBU-Warnt-TB-TXX105010 Version number: 1.0 |
Certificate
|
237 KB |
Herstellererklärung - Made in Germany / Manufacturer‘s Declaration - Made in Germany Type: Certificate Language: International Document number: HK_MiG_OGS-ZEXX113410 Version number: 1.0 |
|
200 KB |
Certificate of Suitability 9133 - SUNNY BACKUP SET M Type: Certificate Language: English (AU) Document number: CoS_SBU5000M_ZAU092010 Version number: 1.0 |
|
82 KB |
Summary Test Report for Compliance to Australian Standards AS4777 - Sunny Backup 5000 / Automatic Switch Box Type: Certificate Language: English (AU) Document number: SBU-AS4777_ZEN083910 Version number: 1.0 |

SMA Feed