Flexible
- Three different power ranges from 30 kW to 300 kW
- Different generators, PV and load magnitudes
Simple
- Integrated AC distribution for Sunny Island, generator, PV
- Integrated load-shedding contactor
Reliable
- Automatic bypass for the generator
- Active Anti-Islanding
- Reverse current monitoring
Durable
- High protection class IP65
- 5-year SMA warranty
| SUNNY ISLAND 5048 Multicluster-Box 6 |
SUNNY ISLAND 5048 Multicluster-Box 12 |
SUNNY ISLAND 5048 Multicluster-Box 36 |
|
| General | |||
| Phase number | 3-phase | 3-phase | 3-phase |
| Nominal AC voltage | 230 V (LN), 400 V (L1, L2) | 230 V (LN), 400 V (L1, L2) | 230 V (LN), 400 V (L1, L2) |
| AC voltage range | 172.5 V – 265 V 300 V – 433 V | 172.5 V – 265 V 300 V – 433 V | 172.5 V – 250 V 300 V – 433 V |
| Nominal AC frequency / range | 50 Hz / 40 Hz ... 70 Hz | 50 Hz / 40 Hz ... 70 Hz | 50 Hz / 40 Hz ... 70 Hz |
| Reliable grid confi guration | TN | TN | TN |
| Dimensions (W / H / D) | 760 / 760 / 210 mm | 1000 / 1400 / 300 mm | 1200 / 2000 / 800 mm |
| Assembly type | Suspended | Standing on base | Standing on base |
| Weight | 60 kg | 140 kg | 400 kg |
| Terminals for Sunny Island | |||
| Maximum number of devices | 6 | 12 | 36 |
| Nominal AC power / nominal AC current at 25 °C | 30 kW / 3 x 44 A | 60 kW / 3 x 87 A | 180 kW / 3 x 260 A |
| Nominal AC power / nominal AC current at 45 °C | 24 kW / 3 x 35 A | 48 kW / 3 x 70 A | 144 kW / 3 x 209 A |
| AC power (25 °C, 30 minutes) | 40 kW | 80 kW | 234 kW / 3 x 340 A |
| AC power (25 °C, 1 minute) | 50 kW | 100 kW | 300 kW / 3 x 440 A |
| Fuses | Miniature circuit-breaker C 32A | Miniature circuit-breaker C 32A | Miniature circuit-breaker C 32A |
| Load connection | |||
| Number | 1 (3-phase) | 1 (3-phase) | 1 (3-phase) |
| Nominal AC power (25 °C, unlimited) | 55 kW | 110 kW | 300 kW |
| Nominal AC current (25 °C) | 3 x 80 A | 3 x 160 A | 3 x 435 A (AC1) |
| Fuses | LV / HRC (size 00) | LV / HRC (size 00) | LV / HRC (size 3) |
| PV plant connection | |||
| Number | 1 (3-phase) | 1 (3-phase) | 1 (3-phase) |
| Nominal AC power (25 °C, unlimited) | 55 kW | 110 kW | 300 kW |
| Nominal AC current (25 °C) | 3 x 80 A | 3 x 160 A | 3 x 435 A (AC1) |
| Fuses | — | — | — |
| Generator connection | |||
| Number | 1 (3-phase) | 1 (3-phase) | 1 (3-phase) |
| Nominal AC power (25 °C, unlimited) | 55 kW | 110 kW | 300 kW |
| Nominal AC current (25 °C) | 3 x 80 A | 3 x 160 A | 3 x 435 A (AC1) |
| Fuses | LV / HRC (size 00) | LV / HRC (size 00) | LV / HRC (size 3) |
| Features | |||
| Warranty (5 / 10 / 15 / 20 / 25 years) | yes / opt. / opt. / opt. / opt. | yes / opt. / opt. / opt. / opt. | yes / opt. / opt. / opt. / opt. |
| Certificates | CE | CE | CE |
| Ambient conditions | |||
| Ambient temperature | -25 °C ... +50 °C | -25 °C ... +50 °C | -25 °C ... +60 °C |
| Degree of protection (according to IEC 60529) | IP65 | IP65 | IP54 |
| Humidity | 0 % ... 100 % | 0 % ... 100 % | 0 % ... 100 % |
| Accessories | |||
| Communication lines | yes | yes | yes |
| Multicluster Piggy-Back | opt. | opt. | opt. |
| Type designation | MC-Box-6.3 | MC-Box-12.3 | MC-Box-36.3 |
Downloads
Language:
Data sheet
|
698 KB |
Multicluster Boxes for SUNNY ISLAND 5048 - For easy set-up of stand-alone and hybrid systems Type: Data sheet Language: English (AU) Document number: CLUSTBOX-DAU102020 Version number: 2.0 |