SUNNY ISLAND 3324 / 4248 / 4248U

Reliability for small and mid-range systems

The Sunny Islands 3324 and 4248 are outstandingly suited for the installation of small and mid-range stand-alone systems. Energy sources such as solar power, wind energy and hydropower systems can be connected on both the AC and the DC side.

The devices guarantee a reliable, high-quality power supply and operate extremely quietly. We also offer the Sunny Island 4248 as the SI 4248U to US-American specifications.

Usability

  • For systems from 2-5 kW
  • AC and DC coupling
  • Simple installation

 

Efficient

  • High efficiency
  • Excellent price-performance ratio
  • 5 years SMA Warranty
Output data 3324 4248 4248U
Nominal AC voltage 230 V 230 V 120 V
Nominal frequency 50 Hz 50 Hz 60 Hz
Continuous AC output at 25 °C 3300 W 4200 W 4200 W
AC power for 30 min at 25 °C 4200 W 5400 W 5400 W
Input data      
Input voltage 173 - 250 V 173 - 250 V 80 - 150 V
Input frequency 40 - 60 Hz 40 - 60 Hz 54 - 66 Hz
Max. input power 12.8 kW 12.8 kW 6.7 kW
Battery data      
Battery voltage (range) 24 V (21 V - 32 V) 48 V (41 V - 63 V) 48 V (41 V - 63 V)
Continuous charging current 104 A 80 A 80 A
Efficiency    
Max. efficiency (typ.) 94.5 % 95.0 %
Protection class      
per DIN EN 60529 IP 30 IP 30 IP 30
Device protection short-circuit, overload, overheating short-circuit, overload, overheating short-circuit, overload, overheating
General Data      
Dimensions (Width / Height / Depth in mm) 390 / 590 / 245 390 / 590 / 245 390 / 590 / 245
Weight 39 kg 39 kg 39 kg
Operating temperature range –25 °C ... +50 °C –25 °C ... +50 °C –25 °C ... +50 °C
Protection rating Indoors (IP30) Indoors (IP30) Indoors (NEMA 1)
Features / Function      
Operation & display / multifunction relays Internal / 2 Internal / 2 Internal / 2
3-phase systems / parallel connection - / - - / - - / -
Integrated bypass / multicluster operation - / - - / - - / -
State of charge calculation / Full- / Equalization charge - / yes / yes - / yes / yes - / yes / yes
Integrated soft start / Generator support - / - - / - - / -
Battery temperature sensor / Communication cables yes / - yes / - yes / -
Warranty (5 years / 10 years) yes / opt. yes / opt. yes / opt.
Certificates and permits www.SMA.de www.SMA.de www.SMA.de
Accessories      
Battery cables / battery fuses opt. / opt. opt. / opt. opt. / opt.
Interfaces (RS485 PB / Multicluster PB) opt. / - opt. / - opt. / -
GenMan extended generator start opt. opt. opt.
Load-shedding contactor / Battery current measurement opt. / - opt. / - opt. / -
       
Last update: March 2009      
Type Designation SI 3324 SI 4248 SI 4248U

Downloads

Language:
Catalog


4.673 KB

SUNNY ISLAND System Guide - System Solutions for Your Stand-Alone Power Supply
Type: Catalog
Language: English (Worldwide)
Document number: SYSGUIDE-AEN083211
Version number: 1.1


1.970 KB

WINDY BOY - Inverter for Wind Energy Power Plants
Type: Catalog
Language: English (Worldwide)
Document number: WINDYBOY-KEN101613
Version number: 1.3
Data sheet


246 KB

GenMan Basic - SMA´s new off-grid Generator Management Box
Type: Data sheet
Language: English (Worldwide)
Document number: GenMan-12:BE2204


1.367 KB

SUNNY ISLAND 3324 / 4248 / 4248-US - Stand-alone grids simpler than ever
Type: Data sheet
Language: English (Worldwide)
Document number: SI3324_4248-DEN102320
Version number: 2.0
Operating Instructions


978 KB

Sunny Island 3324 / 4248 - Operating Instructions
Type: Operating Instructions
Language: English (Worldwide)
Document number: SI3324_4248-14:FE2406
Version number: 4.0
Installation Guide


910 KB

SUNNY ISLAND 3324 / 4248 - Errata for installation guide
Type: Installation Guide
Language: English (Worldwide)
Document number: SI3324_4248-E-IEN094410
Version number: 1.0


4.886 KB

Sunny Island 3324 / 4248 - Installation Guide
Type: Installation Guide
Language: English (Worldwide)
Document number: SI3324_4248-14:SE2406
Version number: 4.0
Short description


40 KB

Technote: Installer Password for Sunny Island 4248 (U)
Type: Short description
Language: English (Worldwide)
Document number: SI4248_IP-11:EE0305


236 KB

Short Instruction: SI3324/4248/4248U FC in Fuel Cell Applications
Type: Short description
Language: English (Worldwide)
Document number: SI-WR_FC-11:FE0607
Version number: 1.1
Technical Manual


420 KB

Questionnaire on Off-grid System Dimensioning
Type: Technical Manual
Language: English (Worldwide)
Document number: QUESTIONNAIRE-UEN090512d
Version number: 1.2


87 KB

Questionnaire on Off-grid System Dimensioning
Type: Technical Manual
Language: English (Worldwide)
Document number: QUESTIONNAIRE-UEN090512
Version number: 1.2


369 KB

Sunny Island - Sicherheitshinweise / Safety Regulations / Presciptions de Sécurité / Normas de Seguridad / Disposizioni di Sicurezza
Type: Technical Manual
Language: International
Document number: SI-SiHiW-11:XX4405
Version number: 1.1
Technical information


387 KB

PV inverter - Usage and settings of PV inverters in island grids and backup systems
Type: Technical information
Language: English (Worldwide)
Document number: SB-OffGrid-UEN091911
Version number: 1.1
Certificate


580 KB

EC Declaration of Conformity - SUNNY ISLAND 2012, 2224, 3324, 4248, 5048
Type: Certificate
Language: English (Worldwide)
Document number: CE_SI-ZEN094811
Version number: 1.1
Warranty


153 KB

SMA Factory Warranty - Sunny Island/Sunny Backup
Type: Warranty
Language: English (Worldwide)
Document number: GEBED_SI-ZEN095215
Version number: 1.5


157 KB

Order of an Extension of the SMA Factory Warranty
Type: Warranty
Language: English (Worldwide)
Document number: B-GV_ZEN095114
Version number: 1.4
Articles


758 KB

New V/f-Statics controlled Battery Inverter: Sunny Island Author: Mike Meinhardt, Martin Rothert, Alfred Engler
Type: Articles
Language: English (Worldwide)
Document number: SunnyIsland
Practical Example