| Input data | Sunny Central 400HE |
Sunny Central 500HE |
Sunny Central 630HE |
| Nominal power DC | 408 kW | 509 kW | 642 kW |
| Max. PV power (recommended), (PPV) | 450 kWp | 560 kWp | 705 kWp |
| DC voltage range, MPPT (UDC) | 450 V – 820 V | 450 V – 820 V | 500 V – 820 V |
| Max. permissible DC voltage (UDC, max) | 1000 V | 1000 V | 1000 V |
| Max. permissible DC current (IDC, max) | 1000 A | 1200 A | 1350 A |
| Voltage ripple, PV voltage (UPP) | < 3 % | < 3 % | < 3 % |
| Number of fused DC inputs | 2 Connections for external DC main distribution board (SMB) / 8 per potential | 2 Connections for external DC main distribution board (SMB) / 8 per potential | 2 Connections for external DC main distribution board (SMB) / 8 per potential |
| Output data | |||
| Nominal AC output power (PAC) | 400 kW 6) | 500 kW 6) | 630 kW 6) |
| Operating grid voltage ± 10 % (UAC) | 270 V | 270 V | 315 V |
| Nominal AC current (IAC, nom) | 855 A | 1070 A | 1155 A |
| Operating range, grid frequency (fAC) | 50 Hz / 60 Hz | 50 Hz / 60 Hz | 50 Hz / 60 Hz |
| Distortion of the grid current | < 3 % at nominal power | < 3 % at nominal power | < 3 % at nominal power |
| Phase shift (cos φ) | 0.95 leading ... 0.95 lagging |
0.95 leading ... 0.95 lagging |
0.95 leading ... 0.95 lagging |
| Efficiency | |||
| Maximum efficiency PAC, max (η) | 98.6 % | 98.6 % | 98.6 % |
| Euro-Eta (η) | 98.4 % | 98.4 % | 98.4 % |
| Dimensions and Weight | |||
| Width / Height / Depth in mm (W / H / D) | 1600 + 1200/2120/850 | 1600 + 1200/2120/850 | 1600 + 1200/2120/850 |
| Weight approx. (kg) | 1900 | 1900 | 1900 |
| Power consumption | |||
| Internal consumption in operation (Pday) | < 2800 W | < 2900 W | < 3000 W |
| Internal consumption in Standby (Pnight) | < 100 W | < 100 W | < 100 W |
| External auxiliary voltage / grid structure | 3 x 400 V, 50/60 Hz / TN-S, TN-C or TT grid | 3 x 400 V, 50/60 Hz / TN-S, TN-C or TT grid | 3 x 400 V, 50/60 Hz / TN-S, TN-C or TT grid |
| External back-up fuse for auxiliary supply | B 20 A, 3-pole | B 20 A, 3-pole | B 20 A, 3-pole |
| SCC (Sunny Central Control) interfaces | |||
| Communication (NET Piggy Back, optional) | Analog, ISDN, Ethernet | Analog, ISDN, Ethernet | Analog, ISDN, Ethernet |
| Analog inputs | 1 x PT 100, 3 x Ain | 1 x PT 100, 3 x Ain | 1 x PT 100, 3 x Ain |
| Overvoltage protection for analog inputs | Optional | Optional | Optional |
| Sunny String-Monitor connection (COM1) | RS485 | RS485 | RS485 |
| PC connection (COM3) | RS232 | RS232 | RS232 |
| Electrically separated relay (ext. alert signal) | 1 | 1 | 1 |
| Features | |||
| Display (SCC) | Yes | Yes | Yes |
| Ground fault monitoring | Yes | Yes | Yes |
| Heating | Yes | Yes | Yes |
| Emergency stop | Yes | Yes | Yes |
| Power switch AC side | Fuse switch disconnector | Fuse switch disconnector | Fuse switch disconnector |
| Power switch DC side | Load disc. switch with motor | Load disc. switch with motor | Load disc. switch with motor |
| Monitored overvoltage protectors AC / DC | Yes / Yes | Yes / Yes | Yes / Yes |
| Monitored overvoltage protectors for aux. supply | Yes | Yes | Yes |
| Standards | |||
| EMC | EN 61000-6-2, EN 61000-6-4 |
EN 61000-6-2, EN 61000-6-4 |
EN 61000-6-2, EN 61000-6-4 |
| Grid monitoring | in acc. with BDEW directive | in acc. with BDEW directive | in acc. with BDEW directive |
| CE conformity | Yes | Yes | Yes |
| Protection rating and ambient conditions | |||
| Protection rating as per EN 60529 | IP20 | IP20 | IP20 |
| Protection rating per EN 60721-3-3 Ambient Conditions: fixed location, weather protection |
Classification of •chem. active substances: 3C1L •mech. active substances: 3S2 |
Classification of •chem. active substances: 3C1L •mech. active substances: 3S2 |
Classification of •chem. active substances: 3C1L •mech. active substances: 3S2 |
| Permissible ambient temperatures (T) | –20 °C ... +50 °C | –20 °C ... +50 °C | –20 °C ... +50 °C |
| Relative humidity, non condensing (UAIR) | 15 % ... 95 % | 15 % ... 95 % | 15 % ... 95 % |
| Max. altitude (above sea level) | 1000 m | 1000 m | 1000 m |
| Fresh air consumption (VAIR) | 6200 m³/h | 6200 m³/h | 6200 m³/h |
| Type designation | SC 400HE-11 | SC 500HE-11 | SC 630HE-11 |
Downloads
Language:
Catalog
|
147 KB |
SMA Solar Technology Productfinder Type: Catalog Language: English (Worldwide) Document number: PRODUCTFINDER-AEN083211 Version number: 1.1 |
|
6.369 KB |
SUNNY CENTRAL 2009/2010 - Highest yields. For all utility grids. Type: Catalog Language: English (Worldwide) Document number: SUNCENT-KEN092021 Version number: 2.1 |
Data sheet
|
111 KB |
EVR "Extended Voltage Range" Technical Data Type: Data sheet Language: English (Worldwide) Document number: SC-EVR-11BE0507 Version number: 1.1 |
|
459 KB |
SUNNY CENTRAL 200HE / 250HE / 350HE - Optimal solution for direct feeding to a medium-voltage grid Type: Data sheet Language: English (Worldwide) Document number: SC200HE_350HE-DEN090714 Version number: 1.4 |
|
218 KB |
Sunny Central SC150 - Data Sheet Type: Data sheet Language: English (Worldwide) Document number: SC150-26BE3507 Version number: 2.6 |
|
364 KB |
SUNNY CENTRAL - Our service – exactly what you need Type: Data sheet Language: English (Worldwide) Document number: SCSERVICE-DEN100620 Version number: 2.0 |
|
418 KB |
SUNNY CENTRAL 500HE / 560HE - Optimal solution for direct feeding to a medium-voltage grid Type: Data sheet Language: English (Worldwide) Document number: SC500HE_560HE-DEN090715 Version number: 1.5 |
|
491 KB |
SUNNY CENTRAL 500HE / 560HE - Optimal solution for direct feeding to a medium-voltage grid (Bulgarian) Type: Data sheet Language: International Document number: SC500HE_560HE-DBG090714 Version number: 1.4 |
User Manual
|
25 KB |
Transfer of Sunny Central Lists to Sunny Portal Type: User Manual Language: English (Worldwide) Document number: SCtoSP-11:NE4406 Version number: 1.0 |
Installation Guide
|
248 KB |
SUNNY CENTRAL 500HE - Installation Near the Sea Type: Installation Guide Language: English (Worldwide) Document number: SC500_Meer-IEN083910 Version number: 1.0 |
Technical information
|
253 KB |
COM-C - Communication distribution box for large-scale PV plants with Sunny Central or Sunny Mini Central Type: Technical information Language: English (Worldwide) Document number: COM-C-UEN093320 Version number: 2.0 |
|
396 KB |
Sunny Main Box - Connecting the DC cabling for PV inverters Type: Technical information Language: English (Worldwide) Document number: SMB-UEN093321 Version number: 2.1 |
|
876 KB |
Sunny Main Box Cabinet - Connecting the DC cabling for PV inverters Type: Technical information Language: English (Worldwide) Document number: SMB-C-UEN093120 Version number: 2.0 |
|
722 KB |
Transport requirements - for SUNNY CENTRAL Type: Technical information Language: English (Worldwide) Document number: SC-TB-UEN092711 Version number: 1.1 |
|
266 KB |
SUNNY CENTRAL - Effect on radio and television reception by the Sunny Central for all solar power systems with SUNNY CENTRAL Type: Technical information Language: English (Worldwide) Document number: EMV_SC-UEN091910 Version number: 1.0 |
|
417 KB |
SUNNY CENTRAL - Notes for grounded operation of the PV generator Type: Technical information Language: English (Worldwide) Document number: SC-HEM-UEN083710 Version number: 1.0 |
Technical Description
|
1.561 KB |
SUNNY MAIN BOX - Connection of the DC-cabling for the PV-inverters SC Type: Technical Description Language: English (Worldwide) Document number: SMB-TEN083810 Version number: 1.0 |
|
147 KB |
Measuring equipment for the Sunny Central Type: Technical Description Language: English (Worldwide) Document number: SCMess-10:BE:3406 Version number: 1.0 |
Certificate
|
2.318 KB |
EC Declaration of Conformity - SUNNY CENTRAL Type: Certificate Language: English (Worldwide) Document number: CE_SCLVHE-ZEN092910 Version number: 1.0 |
Warranty
|
682 KB |
SMA Factory Warranty - SUNNY CENTRAL Type: Warranty Language: English (Worldwide) Document number: GEBED_SC-ZEN094217 Version number: 1.7 |
White Paper
|
73 KB |
Description of Grid Monitoring and Active Islanding Detection Type: White Paper Language: English (Worldwide) Document number: WhitePaper_FFi_Antiislanding_EU-Geraete_E Version number: 1.0 |
References
|
471 KB |
Photovoltaic Ground Mounted System Kaufbeuren > Germany Type: References Language: English (Worldwide) Document number: KAUFBEUREN-AEN074711 Version number: 1.1 |
|
516 KB |
Manufacturing Building Memmingen > Germany Type: References Language: English (Worldwide) Document number: MEMMINGEN-AEN074711 Version number: 1.1 |
|
313 KB |
Turkey Farm Swabian Mountains > Germany Type: References Language: English (Worldwide) Document number: PUTENSTALL-AEN074711 Version number: 1.1 |
|
239 KB |
Solar Park - Oberndorf > Germany Type: References Language: English (Worldwide) Document number: SOLARPARK-AEN091012 Version number: 1.2 |

SMA Feed