Step 1.
Calculate the maximum string current
It is typical for arrays connected to SMA inverters to be installed without DCU (DC conditioners/optimisers).
AS/NZS 5033:2021 3.3.3 (a) describes how to calculate ISTRING MAX where no DCU are installed.
ISTRING MAX = 1.25 x KI x ISC MOD
Generally, KI has a value of 1 except where bifacial modules are used.
ISC MOD is the STC short circuit current of the PV module in Amps.
It will be available from the PV module datasheet.
Step 2.
Check backfeed current of inverter MPPT DC input.
ISTRING = ISTRING MAX or IBF TOTAL (whichever is greater)
IBF TOTAL is the backfeed current from sources other than the PV Array. It can be ignored with the SMA inverters listed in Table 1. These inverters produce zero backfeed current so IBF TOTAL will always be less than ISTRING MAX. Backfeed current is termed ‘maximum reverse current’ in SMA inverter manuals.
Step 3.
Calculate the maximum array current
IARRAY = SA x ISTRING MAX
IARRAY is the maximum array current in Amps.
SA is the number of strings in the array.
ISTRING MAX is the maximum current per string in Amps.
Step 4.
Confirm the maximum array current is less than the inverter MPPT DC input ISC.